CLASS 2, COPPER CONDUCTOR, PVC INSULATED, STEEL WIRES ARMOURED, PVC SHEATHED - DVV/SWA
TECHNICAL CHARACTERISTICS
- Rated voltage U0/U: 0,6/1 kV.
- Maximum conductor temperature for normal operation is 75oC.
- Maximum permissible temperature when not exposed to
mechanical deformation is 90oC. - Maximum conductor temperature for short-circuit (5s maximum
duration) is 160oC. - Minimum bending radius:
*Installed cables: 12 x D (D: overall diameter of cable).
STANDARD
- AS/NZS 5000.1
- AS/NZS 1125
- AS/NZS 3808
IDENTIFICATION
- 2 cores: identified by numbers (01, 02), black numbers shall be
printed on surface of white Insulation of cores - 3 cores & more: identified by numbers (01, 02…), black numbers
shall be printed on surface of white Insulation of cores combine
with a core in yellow-green color (green Insulation with yellow
stripes). - Number of cores: 3, 5, 7, 9, 11, 13, 26, 31, 36, 41.
- Outer sheath: Black or Orange
APPLICATION
-
For control circuits unenclosed, enclosed in conduit, buried
direct or in underground ducts for commercial, industrial, mining
and electricity authority systems where mechanical damage
may occur.
CONSTRUCTION
- Conductor: Annealed copper wire (class 2)
- Insulation: PVC (Type 5V-90)
- Filler: PP (if necessary)
- Inner sheath: PVC (Type 5V-90)
- Armour: Steel wire armour
- Sheath: PVC (Type 5V-90)

THÔNG SỐ KỸ THUẬT