CLASS 2, COPPER CONDUCTOR, PVC INSULATED, PVC SHEATHED - DVV
TECHNICAL CHARACTERISTICS
- Rated voltage U0/U: 0,6/1 kV.
- Maximum conductor temperature for normal operation is 75oC.
- Maximum permissible temperature when not exposed to
mechanical deformation is 90oC. - Maximum conductor temperature for short-circuit (5s maximum
duration) is 160oC. - Minimum bending radius: Installed cables: 12 x D (D: overall
diameter of cable).
STANDARD
- AS/NZS 5000.1
- AS/NZS 1125
- AS/NZS 3808
IDENTIFICATION
- 2 cores: identified by numbers (01, 02), black numbers shall be
printed on surface of white Insulation of cores - 3 cores & more: identified by numbers (01, 02…), black numbers
shall be printed on surface of white Insulation of cores combine
with a core in yellow-green color (green Insulation with yellow stripes). - Number of cores: 2, 3, 4, 7, 8, 10, 12, 19, 20.
- Outer sheath: Black or colour as order
APPLICATION
DVV control cables are used for control circuits, rated voltage 0,6/1
kV – 50Hz, fixed wiring. Laid on cable ladder, tray, in duct in a thermal
Insulation wall, on a wall or spaced from wall, on the dry and closed
cable trench in workshops, building; from source to machine or
device, in duct in the ground…
CONSTRUCTION
- Conductor: Annealed copper wire (class 2)
- Insulation: PVC (Type V-90)
- Filler: PP (if necessary)
- Sheath: PVC (Type 5V-90)

SPECIFICATIONS